Riser Testing
The person responsible for a building or site is legally required to maintain
all fire fighting
equipment, including dry risers. The British Standard Code of Practice BS9990:2006
requires
a full annual pressure test and six monthly visual check for dry risers for
buildings above
18 metres and below 60 metres (buildings over 60 metres/18 storeys require
wet risers).
The standard states
that inlets, landing valves, drain valves and landing valve boxes should
be inspected every 6 months and recommends that wet tests be carried out annually
when
the main can be checked for leaks.
BS9990:2006 also states
that maintenance and repairs should be carried out by a competent
person. With Lindum Fire Services Ltd you can be confident that all work will
be carried out in
accordance with the British Standards. We are registered with BAFE, members
of the British
Fire Consortium and hold the British Standard Kitemark.
Dry Riser Testing
- Maintenance & Servicing
Dry Risers
are a important piece of fire protection equipment for buildings above 18
metres.
They play a critical role in delivering considerable quantities of water in
a high rise building.
They can however be prone to serious neglect and vandalism so it is important
to have them
regularly maintained and serviced. We will carry out a full annual pressure
test and six monthly
visual check to the current British Standard Code of Practice BS9990:2006
using our own dry
riser testing appliance.
Dry Riser
Testing - Annual Wet Test
Dry and
wet risers are checked and pressure tested to 150 PSL or 10 bar for a minimum
of
15 minutes. All insets and outlets are checked for leaks and any missing or
faulty items
replaced. Flow testing is also carried out. If any valves have to be replaced
a further
pressure test will be carried out before certification is issued.
Dry Riser
Testing - Six Monthly Visual Test
This test involves a visual
inspection only as required by BS9990:2006 and any missing or damaged items
are replaced.
Private
Fire Hydrant Test
For large
premises with hydrants on sites, Lindum Fire Services Ltd will test flow rates
and Static pressure test, also carry out a visual inspection of the location,
H plate, cover and frost valve. BS9990:2006 clause 7 requires checking of
pits, frames, covers and surface paving round edges of frames.